    HV self-regulating &  middle temperature electric heating cable

    SPECIFICATION:
    Self-regulating and save energy
    Voltage  220V/110V
    Max Using Length  120 m
    Max Heat tracing Temperature  110℃
    the most Suitable Temperature for heat tracing  80℃
    Outline Size 4.6×11.7 mm
    Local Cutting at random
    28 W/m、41W/m(10℃)
    Min. Bending Radius 30mm
    Fitting for Explosion-proof Area 1、2
    Temperature group T4
    Heat Output for Cable W/m
    A 14AWG Copper Bus Wires
    B Semiconductor Heating Core
    C Insaluting Jacket

    D Tinned Copper Braid

    E Overjacket(optional)
    Type
    Output Power
    45HV-2SJ
    45.0-0.37Tp
    30HV-2SJ
    30.3-0.24Tp
    Record:Tp is the pipe temperature
    Circuit  breaker selection(Unit: Meter)
    Cable
    Type
    Openning Temp.10℃
    Openning Temp.-10℃
    Openning Temp.-30℃
    15A
    20A
    30A
    40A
    15A
    20A
    30A
    40A
    15A
    20A
    30A
    40A
    50A
    30HV-2SJ
    43
    57
    86
    114
    39
    52
    78
    104
    36
    49
    72
    98
    120
    45HV-2SJ
    38
    51
    76
    100
    36
    48
    72
    96
    33
    44
    66
    88
    100
     Suggestion:  PLS using the thermal magnetic circuit breaker . For it can “nuisance trip” at low temperature.