    HHV self-regulating & high temperature electric heatingcable

    SPECIFICATION:
    Self-regulating and save energy
    16 AWG Conductor
    Rated Voltage  220V/110V
    Max Using Length  69m
    Max Heat tracing Temperature  190℃
    The most Enduring heating Temperature  232℃
    Local Cutting at random
    60W/m、75W/m、90W/m
    Min. Bending Radius 30mm
    Fitting for Explosion-proof Zone 1、2
    A Bus wires
    B Semiconductor Heating Core
    C Inner Jacket,Improving FI Plastic

    D Tinned Copper Braid,nickel ,chrome, copper or Stainless Steel Braid

    E FI Plastic Overjacket
    Power Amending Quotiety
    NO.
    208V
    277V
    20HHV
    0.94
    1.08
    30HHV
    0.99
    1.01
    Circuit breaker selection (Unit: Meter)
    Cable
    Type
    Openning Temp.10℃
    Openning Temp.-20℃
    Openning Temp.-45℃
    15A
    20A
    30A
    15A
    20A
    30A
    15A
    20A
    30A
    20HHV-2SJ
    34
    45
    69
    33
    43
    66
    31
    42
    63
    25HHV-2SJ
    27
    36
    51
    24
    30
    48
    24
    30
    48
    30HHV-2SJ
    24
    30
    42
    21
    27
    42
    21
    27
    42
     Suggestion:  PLS using the thermal magnetic circuit breaker . For it can “nuisance trip” at low temperature.
    Type Number Nomenclature:

        
    ISO9001、Ex、ATEX、FM、EAC、CE、UL、WPQR(Comply With PED、ASME)    